Two different concepts, both fundamental to fire safety.
Describes the behaviour of a material when exposed to a heat source in the ignition phase of a fire.
It measures whether, and how much, the material:
A1 · A2 · B · C · D · E · F
(+ subclasses s1–s3 for smoke, d0–d2 for flaming droplets)
Describes the ability of a building element to maintain its functions during a fully developed fire.
It measures for how long the element:
R / RE / REI / EI / EW · 30 → 240 min
E.g. EI 120 = 120 minutes of integrity + insulation
A material with a poor reaction-to-fire class can still be used within a system of high fire resistance, provided it is protected. Conversely, a non-combustible (A1) material does not in itself guarantee fire resistance: an A1 board fixed to a poor frame fails quickly.
Global Building FIREGUARD boards are Euroclass A1 (reaction to fire) and are built into systems certified EI up to 240 minutes (fire resistance). The two performances add up: the system is safe in the ignition phase and resistant in the fully developed phase.
It depends on the type of occupancy and the performance level required by the Italian Fire Prevention Code (D.M. 3/08/2015):
Technical support
The Global Building technical department can help you identify the class the regulations require and the correct certified solution for your occupancy.