inspection hatch for plasterboard or calcium silicate walls with fire resistance EI 60 / 90 / 120

INSPECTION HATCH made of aluminium profiles welded using a special process, with a removable door. The “GB-EI 120 PARETE” wall hatch consists of: – a fixed perimeter frame made of aluminium angle profiles, nominal section 30x25 mm and nominal thickness 2 mm, fitted with 2 snap locks. – a door made of a calcium silicate and calcium sulphate board called FIREGUARD® fixed to a perimeter frame made of aluminium angle profiles, with nominal section 30x25 mm and nominal thickness 2 mm. – a graphite-based intumescent gasket called “GB-TE”, nominal section 20x1,5 mm, applied along the perimeter of the door facing the fixed perimeter frame. The hatch is installed by making a hole in the supporting wall with dimensions equal to those of the door + 60 mm. Insert the hatch through the opening made in the wall and fix the outer frame to the plasterboard wall with self-tapping screws. Depending on the size of the inspection hatch, 2 to 3 screws per side must be used. Fill the joint between the frame and the plasterboard wall, including the screws, using gypsum-based filler. Once filling is complete, clean any residue off the outer frame, attach the safety cable and close the hatch. In the case of installation on walls of smaller thickness, a special spacer element must be fitted between the boards and the perimeter frame of the hatch, in order to make the hatch perfectly flush with the wall. If a “shimming kit” is supplied, the elements (boards) must be screwed to the perimeter frame before insertion into the housing hole.
The contents of this page are summarised from the official technical data sheet PDF, which remains the reference document.