Application
Structural Protection: Steel Structures · Steel Beams

Supply and installation of protection for steel beams with fire resistance R15/30/45/60/90/120/180/240, made with FIREGUARD® boards, thickness… (see tables), maximum dimensions 1200x2000 mm, made of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, approved in reaction-to-fire class A1 (non-combustible), in accordance with assessment report Applus 11-2720-730 M1 according to standard EN 13381-4.
The boards will be applied with phosphated self-drilling screws, diameter 3,5 mm, of suitable length, at 250 mm centres, to vertical “C” stud profiles 75x50x0,6 mm positioned at the sides of the beam at 550 mm centres, inserted into “U” tracks 75x40x0,6 mm positioned at the ceiling and at the lower part of the beam. The joints and screw heads will be finished with FIREGUARD COMPOUND filler.