Fire protection for electrical cables certified EI 60 (ho i→o) and EI 120 (ho i←o). Suitable for outdoor use, particularly for photovoltaic systems where resistance to UV radiation and weathering is required.
Canalina portacavi ispezionabile per ambienti esterni, resistente ai raggi UV e alle intemperie; EI 60 (hₒ i→o) ed EI 120 (hₒ i←o).

Accessible cable duct made from two 12.7 mm layers of Fireguard 13 calcium silicate and calcium sulphate board. The asbestos-free boards are manufactured by lamination with controlled factory drying and have an A1 (non-combustible) reaction-to-fire classification. A steel casing protects the duct against weathering and UV radiation. A rain baffle provides weather protection while allowing ventilation to prevent overheating caused by live cables. The 1.2 m sections have interlocking connections. They can be installed as individual sections on roofs where cables pass through compartment walls, or as a continuous system for electrical cable protection.
Fit galvanised steel crossmembers at centres less than 1.1 m apart. Install the lower steel casing, including the end pieces, and insert the U-shaped calcium silicate section. Lay the cables and service components and fit the calcium silicate lid. Install the upper steel casing and fasten it to the lower casing with screws and bolts. For continuous cable protection, join the calcium silicate sections at the joints using phosphated self-drilling screws.
The contents of this page are summarised from the official technical data sheet PDF, which remains the reference document.