inspection hatch for REI 120 suspended ceilings in calcium silicate

The hatch consists of: – a fixed perimeter frame made of aluminium angle profiles, nominal section 30x12 mm and nominal thickness 2 mm, fitted with 2 snap closures. – a door made with a calcium silicate and calcium sulphate board named FIREGUARD® 13, nominal thickness 12,7 mm and nominal weight 10,2 kg/m2, fixed to a perimeter frame made of aluminium angle profiles, with nominal section 30x12 mm and nominal thickness 2 mm. – a safety cable (from size 300x300 upwards). – the hatch includes 85 mm wide FIREGUARD® 13 packing strips and a hatch cover.
The hatch is installed by cutting an opening in the suspended ceiling measuring the size of the frame +85 mm and fitting the 50x27x0,6 mm “C” profiles around the opening, at a distance of 60 mm from the opening itself. Line the internal vertical sides of the opening with one layer of FIREGUARD® 13 boards, 12,7 mm thick, to a height of 50 mm, screwing the boards to the 50x27x0,6 mm “C” profiles. Position a cover made of one layer of FIREGUARD® 13 boards simply resting on the opening. Take the inspection hatch, insert it through the opening cut in the suspended ceiling and fix the outer frame with phosphated self-drilling screws. Seal the perimeter of the frame to the suspended ceiling with Fireguard Compound, including the screws. Once the sealing is complete, clean any residues off the outer frame, attach the safety cable and close the hatch.
The contents of this page are summarised from the official technical data sheet PDF, which remains the reference document.