Application
Structural Protection: Reinforced Concrete · R.C. Columns

| T (min) | 30’ | 60’ | 90’ | 120’ | 180’ | 240’ |
| t (mm) | 51 | 61 | 68 | 68 | 61 | 38 |
Supply and installation of protection for reinforced concrete columns with fire resistance R 30/60/90/120/180/240, made with FIREGUARD® boards, thickness… mm (see tables), maximum dimensions 1200x2000 mm, made of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction-to-fire class A1 (non-combustible), in accordance with assessment report ITB 03061-A2/25 according to standard EN 13381-3.
The boards will be applied with metal expansion anchors, diameter 6 mm, length 40 mm, at 500 mm centres. The joints and anchor heads will be finished with FIREGUARD COMPOUND filler.