Application
Vertical Compartmentation · Upgrading Of Plasterboard Walls

Supply and installation of the upgrading of plasterboard walls with EI 120 fire resistance. The existing plasterboard wall is composed of vertical “C” stud profiles 50x50x0,6 mm at 600 mm centres and horizontal “U” track profiles 50x40x0,6 mm positioned at floor and ceiling, clad with one standard plasterboard sheet, 12,5 mm thick, per side. The cladding of the wall on the side exposed to fire will be made with two FIREGUARD® 13 boards, 12,7 mm thick, maximum dimensions
produced by lamination with factory-controlled drying, in reaction-to-fire class A1 (non-combustible), in accordance with classification report I.G. 268751/3193FR. The boards will be applied on the side exposed to fire, laid horizontally, with phosphated self-drilling screws, 3,5 mm diameter, 35 mm long at 600 mm centres for the inner layer, 45 mm long at 250 mm centres for the outer layer, fixed to the metal profile.