Application
Horizontal Compartmentation - Suspended Ceilings · Protection Of R.C. And Prestressed R.C. Roof Units With Lowered Suspended Ceiling

Supply and installation of a suspended ceiling under reinforced or prestressed concrete roof units with fire resistance REI 120 positioned 200 mm below the soffit of the beams, made with FIREGUARD® 13 boards, 12,7 mm thick, maximum dimensions 1200x2000 mm, made of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in class A1 (non-combustible) reaction to fire in accordance with classification report I.G. 300967/3491FR. The boards will be screw-fixed with phosphated self-drilling screws, diameter 3,5 mm,
length 25 mm, at 250 mm centres, to a metal structure composed of a secondary framing consisting of galvanised steel “C” profiles, dimensions 50x27x0,6 mm, at 500 mm centres, and a primary metal framing consisting of the same “C” profiles at 900 mm centres, fixed to the secondary framing by means of special orthogonal clips and suspended with hangers at 900 mm centres. The joints and screw heads will be finished with FIREGUARD COMPOUND filler.