Application
Horizontal Compartmentation - Suspended Ceilings · Vertical Membrane Bulkhead

Supply and installation of a vertical membrane bulkhead with EI 60 (a←b) fire resistance, made with FIREGUARD® S boards, thickness 8 mm, maximum dimensions 1200x2400 mm, made of cement-matrix silicates, asbestos-free, certified in reaction-to-fire class A1 (non-combustible), in conformity with classification report I.G. 3310251/3594FR. The boards will be installed horizontally with phosphated self-drilling screws, diameter 3,5 mm, length 25 mm at 200 mm centres, to “C”-shaped
metal profiles 75x50x0,6 mm placed at 400 mm centres, inserted into and fixed by means of steel screws to “U”-shaped tracks 75x40x0,6 mm placed at the ceiling and at the base of the bulkhead. A rock mineral wool blanket, thickness 30+30 mm, density 60 kg/m³, will be inserted in the cavity. The joints and the screw heads will be finished with FIREGUARD COMPOUND filler.