Application
Ventilation Ducts · Horizontal Ventilation Ducts

Supply and installation of horizontal ventilation ducts with fire resistance EI 120 (ho i→o) and EI 180 (ho i←o) S; made with FIREGUARD DUCT boards, thickness 30 mm, max dimensions 1200x2300 mm, made of fibre cement, asbestos-free, in reaction to fire class A1 (non-combustible) in accordance with classification report Tecnalia 13-01484-3-a. The boards will be bonded with FIREGUARD GLUE adhesive and fixed with
phosphated self-drilling screws Ø 5 mm, length 60 mm, at 200 mm centres. The board joints will be covered with FIREGUARD DUCT strips, thickness 30 mm and width 300 mm, fixed with phosphated self-drilling screws Ø 5 mm, length 60 mm, at 250 mm centres and bonded with FIREGUARD GLUE adhesive. The ducts will rest on an “L” profile, dimensions 50x50x5 mm, at 1150 mm centres, fixed to the floor slab with threaded rods 16 mm in diameter.