Application
Protection Of Services · Services Enclosure - Fire Outside

Supply and installation of protection for horizontal ventilation ducts, maximum internal width 1000 mm, with EI 180 (a←b) fire resistance, made with FIREGUARD® 18 boards, thk. 3 x 18,0 mm, composed of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction-to-fire Class A1 (non-combustible), in accordance with classification report I.G. 403548/4303FR. The boards will be laid with staggered joints and fixed with phosphated
self-drilling screws, Ø 3,5 mm, to “L” angle profiles (50x40x0,6 mm) placed at the internal longitudinal corners of the protection. The upper profiles will be fixed to the floor slab with metal anchors, Ø 6 mm, placed at 500 mm centres. At mid-span a “C” profile (50x27x0,6 mm) will be inserted, suspended on hangers at 1000 mm intervals.