Application
Protection Of Services · Services Enclosure - Fire Outside

Supply and installation of horizontal service and electrical installation ducting, maximum internal width 1000 mm, with fire resistance EI 180 (a←b), made with FIREGUARD® 18 boards, thickness 3 x 18,0 mm, composed of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction to fire class A1 (non-combustible), in accordance with classification report I.G. 403548/4303FR. The boards will be installed with staggered joints and fixed with phosphated self-drilling
screws Ø 3,5 mm to “L” angle profiles (50x40x0,6 mm) positioned at the internal longitudinal edges of the protection. The upper profiles will be fixed to the floor slab by means of metal anchors Ø 6 mm at 500 mm centres. At mid-span, a “C” profile (50x27x0,6 mm) will be inserted, suspended on hangers at 1000 mm centres.