Application
Protection Of Services · Services Enclosure - Fire Outside

Supply and installation of protection for horizontal ventilation ducts, maximum internal width 500 mm, with EI 180 (a←b) fire resistance, made with FIREGUARD® 18 boards, thk. 3 x 18,0 mm, composed of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction-to-fire Class A1 (non-combustible), in accordance with classification report I.G. 403548/4303FR.
The boards will be laid with staggered joints and fixed with phosphated self-drilling screws, Ø 3,5 mm, to “L” angle profiles (50x40x0,6 mm) placed at the internal longitudinal corners of the protection and at the floor slab, to which they will be fixed with metal anchors, Ø 6 mm, placed at 500 mm centres.