Application
Protection Of Services · Services Enclosure - Fire Outside

Supply and installation of horizontal service and electrical installation ducting, maximum internal width 500 mm, with fire resistance EI 180 (a←b), made with FIREGUARD® 18 boards, thickness 3 x 18,0 mm, composed of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction to fire class A1 (non-combustible), in accordance with classification report I.G. 403548/4303FR.
The boards will be installed with staggered joints and fixed with phosphated self-drilling screws Ø 3,5 mm to “L” angle profiles (50x40x0,6 mm) positioned at the internal longitudinal edges of the protection and at the floor slab, to which they will be fixed by means of metal anchors Ø 6 mm at 500 mm centres.