Application
Structural Protection: Reinforced Concrete · Protection Of R.C. Walls With Carbon Reinforcement

Supply and installation of protection for reinforced concrete walls with carbon reinforcement, with fire resistance REI 120, made with 3 FIREGUARD®13 boards, thickness 12,7 mm, made of calcium silicates and sulphates, asbestos-free, produced by lamination with factory-controlled drying, in reaction-to-fire class A1 (non-combustible), in accordance with classification report I.G. 331596/3771FR and Technical File 399958, application SC09.
The boards will be installed with staggered joints and fixed with phosphated self-drilling screws Ø 3,5 mm to each other and to a supporting framing made of upper and lower “L” angle profiles (40x30x0,6 mm) fixed respectively to the floor slab and to the floor using metal anchors Ø 6 mm at 500 mm centres, so as to create a cavity ≥ 20 mm.