INTUMESCENT WRAP “GB-T”
Application
Penetrations In Reduced-Thickness Walls And Shaft Walls · Penetrations Of Combustible Pipes

Supply and installation of INTUMESCENT WRAP “GB-T” with fire resistance EI 60/90/120 U/C certified on reduced-thickness walls and on partitions made of calcium silicate boards, consisting of intumescent material 50 mm wide, in conformity with classification report ETA 15/0869. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends and inserted into the gap left between the pipe and the partition. For seals with fire resistance class EI 60/90 it is necessary to box out the opening externally until a minimum thickness of 40 mm is reached.
For seals with fire resistance class EI 120 it is necessary to box out the opening externally until a minimum thickness of 80 mm is reached and to insert the wrap on both sides of the partition. It is necessary to apply the indicated number of layers according to the diameter of the pipe. The seal between the pipe and the wall can be closed with dimensionally stable non-combustible material such as concrete, cement mortar or gypsum mortar, through the full thickness of the building element.