FIRE COLLARS “GB-C EXTRA PLUS”
Application
Wall Penetrations · Penetrations Of Combustible Pipes

Supply and installation of FIRE COLLARS “GB-C EXTRA PLUS” with fire resistance EI 120/240 certified on masonry walls with thickness ≥150 mm, for sealing penetrations of combustible pipes in PVC, PE, PP, ABS, SAN + PVC, consisting of a metal shell 31/41/61/220 mm wide containing intumescent material in accordance with classification report ETA 25/0027.
The collar must be wrapped around the pipe and fixed to the wall on both sides with metal expansion anchors, diameter 6 or 8 mm, in a number depending on the diameter of the pipe to be protected. Before installing the collar, the remaining voids/gaps between the wall and the penetrating pipe must be filled with FIRESTOP SEALANT “GB-MT”.