FIRE COLLARS “GB-C”
Application
Wall Penetrations · Penetrations Of Combustible Pipes

Supply and installation of FIRE COLLARS FOR COMBUSTIBLE PIPES “GB-C” with fire resistance EI 120/240 U/C certified on masonry or plasterboard walls, consisting of a metal shell 25/40/50/60 mm wide containing intumescent material in accordance with classification report ETA 11/0208. The collar must be wrapped around the pipe and fixed to the wall on both sides with metal expansion anchors, diameter 6 or 8 mm, in a number depending on the diameter of the pipe to be protected.
In the case of plasterboard walls, use through threaded rods to fix the two collars. Before installing the collar, the remaining voids/gaps between the wall and the penetrating pipe must be filled with dimensionally stable non-combustible material such as concrete, cement or gypsum mortar, through the full thickness of the building element.