Application
Ventilation Ducts · Horiz. Ventilation Ducts - Fire Inside And Outside

Supply and installation of horizontal ventilation ducts with fire resistance EI 120 (ho i↔o), made with FIREGUARD® 45 boards, thickness 45 mm, maximum dimensions 1200x2000 mm, composed of calcium silicates, asbestos-free, approved in reaction to fire class A1 (non-combustible) in accordance with classification report PK3-01-11- 002-A-1. The boards will be bonded with FIREGUARD GLUE adhesive and fixed with phosphated self-drilling screws diam. 5,0 mm, length 90 mm, at 200 mm centres.
The board joints will be covered with FIREGUARD® S strips, thickness 2x9 mm and width 100 mm, fixed with phosphated self-drilling screws diameter 4,2 mm, length 41 mm, at 100 mm centres and bonded with FIREGUARD GLUE adhesive. The cladding will rest on an “L” profile, dimensions 50x50x5 mm, positioned at the joints at 1200 mm centres and fixed to the floor slab with threaded rods 16 mm in diameter.
Downloads reserved for registered users with a confirmed email address. Register · Sign in