Application
Smoke Extraction Ducts · Horizontal Smoke Extraction Ducts

Supply and installation of horizontal smoke extraction ducts with fire resistance EI 120 (ho i↔o) 500 multi, made with FIREGUARD® 45 boards, thickness 45 mm, maximum dimensions 1200x2000 mm, composed of calcium silicates, asbestos-free, approved in reaction to fire class A1 (non-combustible) in accordance with classification report Applus 12/4798-1532. The boards will be bonded with FIREGUARD GLUE adhesive and fixed with phosphated self-drilling screws diameter 5,0 mm, length 90 mm, at 200 mm centres.
The board joints will be covered with FIREGUARD® S strips, thickness 2x9 mm and width 100 mm, fixed with phosphated self-drilling screws diameter 4,2 mm, length 41 mm, at 100 mm centres and bonded with FIREGUARD GLUE adhesive. The cladding will rest on an “L” profile, dimensions 50x50x5 mm, positioned at the joints at 1200 mm centres and fixed to the floor slab with threaded rods 16 mm in diameter.