“GB-P” PANELS and INTUM. WRAP “GB-T”
Application
Wall Penetrations · Penetrations Of Combustible Pipes

Supply and installation of protection for penetrations of combustible pipes with certified EI 90/120 U/U fire resistance in masonry or plasterboard walls, consisting of INTUMESCENT WRAP “GB-T”, made of intumescent material 50 mm wide, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) treated on both sides with a layer of fire-protection putty, for a panel thickness of 60 mm, in accordance with classification reports ETA 15/0869 and IBS 13050709-3. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of FIRESTOP SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the wall where the cut-out will be fitted.
Fit the cut-out and insert it into the opening with an “interference” fit. Skim the joints with a spatula using the FIRESTOP SEALANT “GB-MT”. It is necessary to position two “GB-P” PANELS butted together. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends, and inserted into the gap remaining between the pipe and the “GB-P” PANELS. Insert the wrap on both sides of the wall. It is necessary to apply the number of layers indicated according to the pipe diameter. For penetrations in plasterboard walls it is necessary to line the internal sides of the opening with gypsum plasterboard to a thickness of at least 20 mm.
Downloads reserved for registered users with a confirmed email address. Register · Sign in