SEALANT “GB-MT GRAPHITE”
Application
Wall Penetrations · Penetrations Of Combustible Pipes

Supply and installation of FIRESTOP SEALANT “GB-MT GRAPHITE” with fire resistance EI 60/120 U/C certified on masonry and plasterboard walls with thickness ≥100 mm, for sealing penetrations of combustible PVC, PE, PP and ABS pipes, in accordance with classification report ETA 21/0114.
The FIRESTOP SEALANT “GB-MT GRAPHITE” will be applied by means of a dedicated gun on both sides of the wall to a depth of at least 25 mm and a maximum width of 30 mm, after inserting on both sides a layer of rock mineral wool 25 mm thick and with a density of 35 kg/m³ (see table).