INTUMESCENT WRAP “GB-T”
Application
Wall Penetrations · Penetr. Of Insulated Non-Combustible Pipes

Supply and installation of INTUMESCENT WRAP “GB-T” with fire resistance EI 120 C/U certified on masonry or plasterboard walls, consisting of intumescent material 50 mm wide, in conformity with classification report ETA 13/0640. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends and inserted into the gap left between the pipe and the wall. Insert the wrap on both sides of the wall. It is necessary to apply the indicated number of layers according to the diameter
of the pipe and the thickness of the insulation. In masonry walls, the outer part of the seal can be closed with dimensionally stable non-combustible material, whereas in the case of plasterboard walls the voids between the wall and the penetrating pipe must be filled with dimensionally stable non-combustible material such as concrete, cement mortar or gypsum mortar, through the full thickness of the building element.