“GB-P” PANELS and WRAP “GB-T”
Application
Wall Penetrations · Penetr. Of Insulated Non-Combustible Pipes

Supply and installation of protection for penetrations of insulated metal pipes with certified EI 120 fire resistance in masonry and plasterboard walls, consisting of INTUMESCENT WRAP “GB-T”, nominal section 40x2 mm, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) 60 mm thick, treated on both sides with a layer of fire-protection coating, in accordance with classification reports I.G. 380080/4093FR and I.G. 380081/4094FR. It is necessary to measure the diameter of the pipe to be protected, including its insulation, and wrap the INTUMESCENT WRAP “GB-T” around the pipe on both sides of the wall for the required number of turns (see table).
Measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of FIRESTOP SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the wall where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the SEALANT “GB-MT”.