“GB-P” PANELS
Application
Wall Penetrations · Penetr. Of Insulated Non-Combustible Pipes

Supply and installation of protection for penetrations of non-combustible pipes insulated with rock mineral wool (density 80 kg/m³) with certified EI 60/180 fire resistance in masonry walls with thickness ≥150 mm, consisting of “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) 60 mm thick, treated on both sides with a layer of fire-protection coating, in accordance with ETA 21/0113. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions
of the opening to be sealed. Apply a small amount of FIRESTOP SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the wall where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the FIRESTOP SEALANT “GB-MT”. For seals with fire resistance class EI 60, position a single “GB-P” PANEL. For seals with fire resistance class EI 120 it is necessary to position two “GB-P” PANELS flush with the two faces of the wall.