“GB-P” PANELS and FIRESTOP SLEEVE “GB-ML”
Application
Wall Penetrations · Penetr. Of Uninsulated Pipes

Supply and installation of protection for penetrations of uninsulated non-combustible or composite pipes with certified EI 90/240 fire resistance in masonry walls, consisting of SLEEVE “GB-ML”, made of a mineral wool felt 500 mm long, thk. 30 mm, density 90 kg/m³, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) 60 mm thick, treated on both sides with a fire-protection coating, in accordance with ETA 21/0113. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of
Firestop SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the wall where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the Firestop SEALANT “GB-MT”. Position one or two “GB-P” PANELS spaced apart (see table). After fitting the “GB-P” PANELS, measure the diameter of the pipe to be protected and cut the quantity of SLEEVE “GB-ML” required to cover it. Wrap the SLEEVE “GB-ML” around the pipe on both sides, butting the joint together and taking care that the sleeve adheres to the “GB-P” PANELS. Secure the SLEEVE “GB-ML” with twisted steel wire ties.