FIRESTOP SLEEVE “GB-ML” and SEALANT “GB-MT”
Application
Wall Penetrations · Penetr. Of Uninsulated Non-Combustible Pipes

Supply and installation of SLEEVE “GB-ML” with fire resistance EI 60/240 C/U certified on masonry walls with thickness ≥150 mm, for sealing penetrations of uninsulated non-combustible pipes, consisting of a mineral wool felt, 500 mm long, thickness 30 mm, density 90 kg/m³, in accordance with classification report I.G. 335023/3808FR and ETA 21/0115. Measure the diameter of the pipe to be protected and cut the quantity of SLEEVE “GB-ML” needed to cover it. Wrap the SLEEVE “GB-ML” in a single/double layer and single/double length (see tables) around the pipe on both sides, butting the joint together and making sure the sleeve adheres to the wall.
Fix the SLEEVE “GB-ML” with twisted steel wire ties. When the SLEEVE “GB-ML” is applied in a single length (500 mm), any free space between the wall and the pipe must be filled on both sides with a layer of rock mineral wool, density 40 kg/m³, to a depth of 20 mm, and a layer of FIRESTOP SEALANT “GB-MT” to a depth of at least 15 mm. When the SLEEVE “GB-ML” is applied in a double length, any free space between the wall and the pipe must be filled on one side with a layer of rock mineral wool, density 40 kg/m³, to a depth of 20 mm, and a layer of FIRESTOP SEALANT “GB-MT” to a depth of at least 15 mm.