SEALANT “GB-MT”
Application
Wall Penetrations · Penetrations Of Insulated Non-Combustible Pipes

Supply and installation of FIRESTOP SEALANT “GB-MT” with fire resistance EI 90/120 certified on masonry and plasterboard walls with thickness ≥100 mm, for sealing penetrations of non-combustible pipes insulated with rock mineral wool or PEX composite pipes, in accordance with classification report ETA 21/0115
The FIRESTOP SEALANT “GB-MT” will be applied by means of a dedicated gun on both sides of the wall to a depth of at least 12,5 mm, after inserting on both sides a layer of rock mineral wool 12,5 mm deep, density 35 kg/m³ (see table).