SEALANT “GB-MT”
Application
Wall Penetrations · Penetrations Of Insulated Non-Combustible Pipes

Supply and installation of FIRESTOP SEALANT “GB-MT” with fire resistance EI 180/240 C/U certified on masonry walls with thickness ≥150 mm, for sealing penetrations of non-combustible pipes insulated with rock mineral wool, in accordance with classification report ETA 21/0115. For seals with fire resistance class EI 180, apply the FIRESTOP SEALANT “GB-MT” by means of a dedicated gun on one side of the wall to a depth of at least 25 mm, after inserting a
layer of AES bio-soluble fibre 48 mm deep (see table). For seals with fire resistance class EI 240, apply the FIRESTOP SEALANT “GB-MT” by means of a dedicated gun on both sides of the wall to a depth of at least 15 mm, after inserting on both sides a layer of rock mineral wool 25 mm deep, with a density of 35 kg/m³ (see table).