Caricamento… / Loading…
INTUMESCENT WRAP “GB-T”
Application
Wall Penetrations · Penetration Of 3 Corrugated Conduits

Supply and installation of INTUMESCENT WRAP “GB-T”, nominal cross-section 40x2 mm, for the protection of penetrations of corrugated combustible pipes (including in groups) with fire resistance EI 120 certified on masonry and plasterboard walls, in conformity with classification report I.G. 380081/4094FR.
It is necessary to measure the diameter of the pipe to be protected and wrap the intumescent gasket around the pipe for the specified number of turns (see table) on the fire-exposed side of the wall.