“GB-P” PANELS
Application
Wall Penetrations · Penetrations Of Electrical Cables

Supply and installation of “GB-P” PANELS with fire resistance EI 60/240 certified on masonry walls with thickness ≥ 150 mm or masonry and plasterboard walls with thickness ≥100 mm, for the sealing of penetrations of electrical cables, single, in bundles or on a cable tray, consisting of semi-rigid mineral fibre panels (density 150 kg/m³), thickness 60 mm, treated on both sides with a fire-protection coating, in conformity with ETA 21/0113. It is necessary to measure the dimensions and shape of the opening to be sealed, mark them on the panel and cut it using site handsaws or a utility knife, taking care to leave the cut-out slightly oversized relative to the dimensions of the opening to be sealed.
Apply a small amount of FIRESTOP Sealant “GB-MT” to the sides of the cut-out or directly to the inner edge of the wall where the cut-out will be applied. Apply the cut-out, fit it into the opening by “interference” and smooth over the joints with a spatula using the FIRESTOP Sealant “GB-MT”. For masonry walls ≥150 mm it is necessary to position one or two “GB-P” panels spaced apart (see table). For masonry and plasterboard walls ≥100 mm it is necessary to position two “GB-P” panels placed against each other.