INTUMESCENT PAINT “GB-PAINT”
Application
Wall Penetrations · Penetr. Of Electrical Cables

Supply and installation of INTUMESCENT PAINT “GB-PAINT” for the protection of electrical cable penetrations with fire resistance EI 120 certified on masonry walls with thickness ≥ 150 mm, on openings protected with “GB-P” semi-rigid mineral fibre panels (density 150 kg/m³), thickness 60 mm, treated on both sides with a layer of fire-protection coating. The INTUMESCENT PAINT “GB-PAINT” may be applied to single electrical cables up to a diameter of 80 mm, bundles of electrical cables up to 100 mm and metal cable trays. The INTUMESCENT PAINT “GB-PAINT” will be applied to the electrical cables and to the metal tray over a length of at least 300 mm and a thickness of 1 mm on both sides of the wall, in conformity with ETA 24/1253.