“GB-P” PANELS and FIRESTOP SLEEVE “GB-ML”
Application
Wall Penetrations · Penetration Of Busbar Trunking

Supply and installation of penetration protection for “Blindosbarra”-type electrical distribution busbars with fire resistance EI 120 certified on plasterboard and masonry walls, made with SLEEVE “GB-ML”, consisting of a mineral wool felt, thickness 30 mm, density 90 kg/m³, and semi-rigid “GB-P” PANELS in mineral fibre (density 150 kg/m³), thickness 60 mm, treated on both sides with a fire-protective coating, in accordance with classification report I.G. 380080/4093FR. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating busbar, transfer them onto the “GB-P” PANELS and cut them using site handsaws or a utility knife, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount
of FIRESTOP SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the wall where the cut-out will be fitted. Fit the cut-out and insert it into the opening by “interference” fit and smooth over the joints with a spatula using the FIRESTOP SEALANT “GB-MT”. After installing the “GB-P” PANELS, measure the dimensions of the busbar to be protected and cut the amount of SLEEVE “GB-ML” needed to cover it. Wrap the SLEEVE “GB-ML” around the busbar on the side of the wall not exposed to fire, butting the joint together and making sure the sleeve adheres to the “GB-P” PANELS. Secure the SLEEVE “GB-ML” with twisted steel wire ties.