GRILLE “GB-GA SLIM”
Application
Wall Penetrations · Fire-Rated Ventilation Grille

Supply and installation of VENTILATION GRILLES “GB-GA SLIM”, with fire resistance EI 120, total thickness 43 mm, certified on masonry or plasterboard walls with a minimum thickness of 120 mm. Consisting of a double layer of cement-matrix silicate boards provided with through holes with a void/solid ratio of 33%, in accordance with classification report I.G. 380080/4093FR.
The grille shall be positioned inside an opening made in the masonry, surrounded by cement-matrix silicate boards with a nominal thickness of 8 mm. The grille shall be faced on both sides with additional aluminium finishing grilles fixed to the supporting construction with self-drilling steel screws.