FIRESTOP BLOCKS “GLOBAL BLOCK”
Application
Multiple Penetrations In Walls · Multiple Penetrations

Supply and installation of INTUMESCENT FIRESTOP BRICKS “GLOBAL BLOCK” with fire resistance EI 45/120 certified on masonry or plasterboard walls, for the sealing of multiple penetrations, consisting of pre-moulded intumescent foam, dim. 144x200x60 mm, in conformity with classification report ETA 10/0431. It is necessary to remove the protective film from the BRICKS “GLOBAL BLOCK” and install them in layers, taking care to fit them perfectly into the opening and to stagger them as in an ordinary masonry wall. Near the penetrating services, cut the BRICKS “GLOBAL BLOCK” to the required size with a knife. Gaps between cables and joints, the
empty areas at cable trays and perimeter seal areas of the opening can be filled using the FOAM “GLOBAL FOAM”, to a filling depth equal to the minimum thickness of the seal. The surface area of the foam may not exceed 400x500 mm, or 0.225 m². For walls with a thickness between 100 and 200 mm, the required seal thickness can be achieved by lining the inner sides of the opening with strips of FIREGUARD® 13 boards, thickness 2x12.7 mm.