Supply and installation of TWO-COMPONENT FIRESTOP FOAM “GLOBAL FOAM” with fire resistance EI 45/120 certified on masonry or plasterboard walls, for the sealing of multiple penetrations, consisting of high-expansion two-component firestop foam, in conformity with classification report ETA 11/0206. It is necessary to fill the opening starting from the rear and working forwards from the bottom upwards. Dispense the foam continuously to prevent it hardening inside the mixing nozzle. After approximately 2 minutes of curing, any foam residues protruding from the opening can be removed by cutting them with a knife. Any cables or pipes installed at a later stage can be routed through the existing foam. Holes left by removed cables or pipes must be filled using the FOAM “GLOBAL FOAM”. If the opening
has large free spaces, these can be filled using the BRICKS “GLOBAL BLOCK”. In the case of rectangular openings with maximum dimensions of 450x500 mm in walls with a thickness between 100 and 144 mm, before installing the FOAM “GLOBAL FOAM” it is necessary to line the sides of the opening with strips of FIREGUARD® 13 boards, thickness 2x12.7 mm, 144 mm wide. In the case of rectangular openings with maximum dimensions of 270x270 mm in walls with a thickness between 100 and 250 mm, the required seal thickness can be achieved by lining the inner sides of the opening with strips of FIREGUARD® 13 boards, th. 2x12.7 mm. Circular openings with a maximum diameter of 300 mm must be boxed out externally with calcium silicate panels in order to achieve the required seal thickness.