“GLOBAL BLOCK” and “GLOBAL FOAM”
Application
Multiple Penetrations In Walls · Penetr. Of Multiple Combustible Pipes

Supply and installation of INTUMESCENT FIRESTOP BRICKS “GLOBAL BLOCK” with fire resistance EI 120 certified on masonry or plasterboard walls, for the sealing of multiple penetrations, consisting of pre-moulded intumescent foam, dim. 144 x 100 x 60 mm, in conformity with classification report I.G. 335023/3808FR and Technical File 399959. It is necessary to line the inner sides of the opening with a triple layer of FIREGUARD® 13 boards, thickness 3x12.7 mm, over a length of 600 mm, and to install the BRICKS “GLOBAL BLOCK” at the two ends of the lining to a thickness of 100 mm. Remove the protective film from the BRICKS “GLOBAL BLOCK” and install them in layers, taking care to fit them perfectly into the opening and to stagger them as in an ordinary masonry wall.
Near the penetrating services, cut the BRICKS “GLOBAL BLOCK” to the required size with a knife. Gaps between cables and joints, empty areas and perimeter seal areas of the opening can be filled using the FOAM “GLOBAL FOAM”, to a filling depth equal to the minimum thickness of the seal. In the case of penetrations of combustible pipes, the INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends and inserted into the gap left between the pipe and the BRICKS “GLOBAL BLOCK”. Insert the wrap on both of the walls formed with the BRICKS “GLOBAL BLOCK”.