INTUMESCENT WRAP “GB-T”
Application
Floor Penetrations · Penetrations Of Combustible Pipes

Supply and installation of INTUMESCENT WRAP “GB-T” with fire resistance EI 90/240 U/C certified on floor slabs, consisting of intumescent material 50 mm wide, in conformity with classification report ETA 15/0869 and Warrington Nr. 14027B. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends and inserted into the gap left between the pipe and the floor slab.
Insert the wrap on the underside of the floor slab. It is necessary to apply the indicated number of layers according to the diameter of the pipe. The outer part of the seal can be closed with dimensionally stable non-combustible material such as concrete, cement mortar or gypsum, through the full thickness of the building element.