“GB-P” PANELS and INTUM. WRAP “GB-T”
Application
Floor Penetrations Floor Penetrations · Penetrations Of Combustible Pipes

Supply and installation of protection for penetrations of combustible PVC pipes with certified EI 90 U/C fire resistance in floor slabs with thickness ≥150 mm, consisting of INTUMESCENT WRAP “GB-T”, made of intumescent material 50 mm wide, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) treated on the outer side with a layer of fire-protection putty, for a panel thickness of 60 mm, in accordance with classification report ETA 21/0113. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANEL and cut it using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of FIRESTOP
SEALANT “GB-MT” to the sides of the cut-out or directly onto the inner edge of the floor slab where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the FIRESTOP SEALANT “GB-MT”. It is necessary to position one “GB-P” PANEL in a central position. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape, and inserted into the gap remaining between the pipe and the “GB-P” PANEL. Insert the wrap inside the “GB-P” PANEL. It is necessary to apply the number of layers indicated according to the pipe diameter (see table).