“GB-P” PANELS and INTUM. WRAP “GB-T”
Application
Floor Penetrations · Penetrations Of Combustible Pipes

Supply and installation of protection for penetrations of combustible pipes with certified EI 90-120 U/U fire resistance in floor slabs, consisting of INTUMESCENT WRAP “GB-T”, made of intumescent material 50 mm wide, and “GB-P” PANELS, semi-rigid mineral fibre (density 150 kg/m³) treated on the outer side with a layer of fire-protection putty, for a panel thickness of 60 mm, in accordance with classification report ETA-15/0869. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating pipe, transfer them onto the “GB-P” PANELS and cut them using hand saws or utility knives, taking care to leave the cut-out slightly oversized with respect to the dimensions of the opening to be sealed. Apply a small amount of firestop sealant “GB-MT” to the sides of the cut-out or directly onto the inner
edge of the floor slab where the cut-out will be fitted. Fit the cut-out and insert it into the opening with an “interference” fit, then skim the joints with a spatula using the firestop sealant “GB-MT”. It is necessary to position two “GB-P” PANELS spaced at least 50 mm apart. The INTUMESCENT WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape to join its ends, and inserted into the gap remaining between the pipe and the “GB-P” PANELS. Insert the wrap on the lower side of the floor slab. It is necessary to apply the number of layers indicated according to the pipe diameter. The outer part of the seal may be closed with Firestop SEALANT “GB-MT” through the full thickness of the building element.