INTUMESCENT PAINT “GB-PAINT”
Application
Floor Penetrations · Uninsulated Non-Combustible Pipes Intumescent Paint ·Gb-Paint·

Supply and installation of INTUMESCENT PAINT “GB-PAINT” for the protection of penetrations of uninsulated non-combustible pipes with fire resistance EI 90/240 certified on floor slabs with thickness ≥ 150 mm. The INTUMESCENT PAINT “GB-PAINT” may be applied both to pipes flush with the opening and to through pipes, on openings protected with “GB-P” semi-rigid mineral fibre panels (density 150 kg/m³), thickness 60 mm, treated on both sides with a layer of fire-protection coating. The INTUMESCENT PAINT “GB-PAINT” will be applied to the non-combustible pipes over a length of at least 500 mm and a thickness of 1 or 2 mm according to the diameter of the pipes (see table) on both sides of the wall, in conformity with ETA 24/1253.