“GB-P” PANELS
Application
Multiple Penetrations In Floors · Multiple Penetrations Panels ·Gb-P·

Supply and installation of “GB-P” PANELS with fire resistance EI 60/240 certified on floor slabs with thickness ≥150 mm, for the sealing of multiple penetrations, consisting of semi-rigid mineral fibre panels (density 150 kg/m³), thickness 60 mm, coated on both sides with a fire-protection coating, in conformity with classification reports ETA 21/0113, I.G. 392775/4207FR, I.G. 392776/4208FR. It is necessary to measure the dimensions and shape of both the opening to be sealed and the penetrating services, mark them on the “GB-P” PANELS and cut the panels using site handsaws or a utility knife, taking care to leave the cut-out slightly oversized relative to the dimensions of the opening to be sealed. Apply a small amount of SEALANT “GB-MT” to the sides of the cut-out or directly to the inner edge of the floor slab where the cut-out will be applied. Apply the cut-out, fit it into the opening by “interference” and smooth over the joints with a spatula using the SEALANT “GB-MT”.
It is necessary to position two “GB-P” PANELS on the two sides of the floor slab. In the case of a penetration of a combustible pipe or of a non-combustible pipe insulated with expanded elastomers, the WRAP “GB-T” must be wrapped around the pipe to be protected, secured with adhesive tape and inserted into the gap left between the pipe and the “GB-P” PANELS. Insert the wrap on both sides of the penetration (see table). It is necessary to apply the indicated number of layers according to the diameter of the pipe. In the case of a penetration of an uninsulated non-combustible pipe, measure the diameter of the pipe to be protected and cut the quantity of SLEEVE “GB-ML” needed to cover it. Wrap the SLEEVE “GB-ML” around the pipe on both sides of the penetration, butting the joint together and making sure that the sleeve adheres to the “GB-P” PANELS. Fix the SLEEVE “GB-ML” with twisted steel wire ties (see table).