FIRE COLLAR “GLOBAL COLLAR PLUS”
Application
Penetrations In Shaft Walls, Suspended Ceilings And Bulkheads · Penetrations Of Combustible Pipes

Supply and installation of UNIVERSAL FIRE COLLAR “GLOBAL COLLAR PLUS” for the protection of combustible pipes, with fire resistance REI120 certified on a 200 mm thick hollow clay block floor slab protected by an accessible suspended ceiling, consisting of a metal shell of thin steel sheet, nominal section 40x30x0,5 mm, containing a graphite-based intumescent gasket, nominal section 40x2 mm, in accordance with ETA 23/0843.
The collar must be installed at the suspended ceiling panelling; to apply the collar, measure the diameter of the pipe to be protected and wrap the intumescent wrap 6 times around the pipe; break off a length of metal sheet sufficient for the overlap and wrap it around the intumescent gasket, fixing it with 4 steel bolts with double nuts secured to the floor slab by means of twisted steel wires, nominal diameter 1 mm, in turn fixed by means of metal expansion anchors.