“GB-P” PANEL and WRAP “GB-T”
Application
Penetrations In Shaft Walls, Suspended Ceilings And Bulkheads · Penetr. Of Insulated Non-Combustible Pipes

Supply and installation of protection for insulated non-combustible pipes with REI120 fire resistance certified on a 200 mm thick hollow clay block floor slab protected by an accessible suspended ceiling, consisting of GB-T INTUMESCENT WRAP composed of intumescent material with a nominal cross-section of 40x2 mm and of semi-rigid mineral fibre GB-P PANEL, 60 mm thick and with a density of 150 kg/m³, treated on both sides with one layer of fire-protection coating, in accordance with classification report I.G. 391407/4196FR.
It is necessary to wrap the intumescent wrap 2 turns around the pipe itself; measure the diameter of the pipe to be protected, including its insulation, transfer it onto the panel, cut it and fit the cut pieces of the GB-P panel over the mineral fibre square.