“GB-P” PANEL and FIRESTOP SEALANT “GB-MT”
Application
Penetrations In Shaft Walls, Suspended Ceilings And Bulkheads · Penetrations Of Electrical Cables

Supply and installation of GB-P PANELS with fire resistance REI120 certified on a 200 mm thick hollow clay block floor slab protected by an accessible suspended ceiling, for the protection of electrical cables, consisting of semi-rigid mineral fibre panels, thickness 60 mm and density 150 kg/m³, treated on both sides with a layer of fire-protection coating, in conformity with classification report I.G. 391407/4196FR.
It is necessary to measure the dimensions of the cables to be protected and mark on the rock mineral wool panel a hole with a diameter increased by 30 mm. Rest the GB-P panel thus obtained on the metal framework of the suspended ceiling, threading the electrical cables through the hole, and seal the remaining space with the acrylic-based elastomeric firestop sealant known as “SEALANT GB-MT”, nominal density 1500 kg/m³, minimum thickness 15 mm.