“GB-P” PANELS and WRAP “GB-T”
Application
Monopanel Penetration · Insulated Non-Combustible Pipes

Supply and installation of protection for insulated metal pipes with EI120 fire resistance certified on sandwich panel walls in accordance with classification report I.G.390859/4193FR. The firestop systems are installed on a double layer of mineral fibre GB-P PANEL, density 150 kg/m3 and thickness 60 mm, treated on both sides with one layer of fire-protection coating; it is necessary to wrap the GB-T INTUMESCENT WRAP 4 turns around the pipe itself; measure the
dimensions and shape of both the opening to be sealed and the penetrating pipe, including its insulation, and transfer them onto the GB-P panels, cut the panels and insert the pieces thus obtained into the opening. The perimeter edges of the seal and the joints between the pieces of the GLOBAL CROSS, or of the GB-P panel, are sealed on both faces with the “GB-MT” sealant.