“GB-P” PANELS and FIRESTOP SLEEVE “GB-ML”
Application
Monopanel Penetration · Uninsulated Non-Combustible Pipes

Supply and installation of protection for uninsulated metal pipes with EI120 fire resistance certified on sandwich panel walls in accordance with classification report I.G.390859/4193FR. The firestop systems are installed on a double layer of mineral fibre GB-P PANEL, density 150kg/m3 and thickness 60mm, treated on both sides with one layer of fire-protection coating; it is necessary to measure the dimensions and shape of both the opening to be sealed and the pipe
and insert the pieces thus obtained into the opening. Finally, wrap the GB-ML SLEEVE around the pipe itself, for a length of 300 mm, on the side not exposed to fire. The perimeter edges of the seal and the joints between the pieces of the GLOBAL CROSS, or of the GB-P panel, are sealed on both faces with the “GB-MT” sealant.