“GB-P” PANELS and WRAP “GB-T”
Application
Monopanel Penetration · Cables And Corrugated Conduits

Supply and installation of protection for electrical cables and combustible pipes containing cables, with certified EI 120 fire resistance in sandwich panel walls, in accordance with classification report I.G.390859/4193FR. The firestop systems are installed on a double layer of GB-P PANEL in mineral fibre, density 150 kg/m3 and thickness 60 mm, treated on both sides with a layer of fire-protection coating; it is necessary to wrap the INTUMESCENT WRAP GB-T 4 turns around
the pipe; measure the dimensions and shape of both the opening to be infilled and the penetrating pipe and transfer them onto the GB-P panels, cut the panels and insert the resulting pieces into the opening. The perimeter edges of the infill seal and the joints between the sections of the GLOBAL CROSS, or of the GB-P panel, are sealed on both faces with the sealant “GB-MT”.