SEALANT “GB-MT”
Application
Expansion Joints · Sealant ·Gb-Mt· Horizontal Expansion Joints Wall/Floor

| Joint width | Joint orientation | “GB-MT” thickness | Seal (infill) | Supporting construction | Classification | Certificate |
| ≤ 30 mm | Vertical on vertical construction | 12,5 mm on two sides | rock mineral wool th. 20 mm, density 35 kg/m³ | Masonry or concrete walls with th. ≥ 150 mm, density ≥ 650 kg/m³ | EI 120 V-X-F-W00 to 30 | ETA 21/0319 |
Supply and installation of protection for vertical expansion joints between walls and walls: - with a maximum width of 30 mm, fire resistance EI 120 V-X-F-W00 to 30, with movement capability of up to 7,5%, consisting of a layer of rock mineral wool, thickness 20 mm, density 35 kg/m3, and a layer of FIRESTOP SEALANT “GB-MT”, thickness 12,5 mm, on two sides. - with a maximum width of 15 mm, fire resistance EI 90 V-X-F-W15, with movement capability of up to 7,5%, consisting of a layer of FIRESTOP SEALANT “GB-MT”, thickness 12,5 mm (see table). In accordance with classification report ETA 21/0319.
In the case of a masonry wall (not plasterboard), the rock mineral wool panels must be inserted into the joint by light compression, where they will remain fixed, partly returning to their original size due to spring-back expansion. Seal the joints externally by applying a layer of FIRESTOP SEALANT “GB-MT” of suitable thickness.