SEALANT “GB-MT”
Application
Expansion Joints · Horizontal Expansion Joints Floor/Wall

| Joint width | Joint orientation | “GB-MT” thickness | Seal (infill) | Supporting construction | Classification | Certificate |
| ≤ 30 mm | Horizontal on vertical construction | 12,5 mm on two sides | rock mineral wool th. 12,5 mm, density 35 kg/m³ + 50 mm steel head profile | Concrete floor slabs with th. ≥ 150 mm, density ≥ 650 kg/m³ · Plasterboard walls with th. ≥ 100 mm, 2 boards per side | EI 120 T-X-F-W00 to 30 | ETA 21/0319 |
| ≤ 30 mm | Horizontal on vertical construction | 25 mm on two sides | 50 mm steel head profile | Concrete floor slabs with th. ≥ 150 mm, density ≥ 650 kg/m³ |
Supply and installation of protection for horizontal expansion joints between plasterboard walls and floor slabs, with a maximum width of 30 mm, EI 120 T-X-F-W00 to 30 fire resistance, with movement capability of up to 7,5%, made of a layer of rock mineral wool, thk. 12,5 mm, density 35 kg/m3, and a layer of Firestop SEALANT “GB-MT”, minimum thk. 12,5 mm, in accordance with classification report ETA 21/0319. The rock mineral wool panels must be inserted on both sides of the joint by light compression, where they will remain fixed, partially returning
to their original dimensions due to recovery expansion. Seal the joint externally by applying on both sides a layer of Firestop SEALANT “GB-MT” with a thickness of at least 12,5 mm. Alternatively, the joint may be sealed by applying only the layer of Firestop SEALANT “GB-MT”, on both sides, to a thickness of at least 25 mm.
| EI 120 T-X-F-W00 to 30 |
| ETA 21/0319 |
| ≤ 25 mm | Horizontal on vertical construction | 12,5 mm on two sides | 50 mm steel head profile | Plasterboard walls with th. ≥ 100 mm, 2 boards per side | EI 90 T-X-F-W00 to 30 | ETA 21/0319 |